INSTRUCTIONS
ABOUT THE ACTIONS OF EMPLOYEES IN THE PREMISES,
EQUIPPED WITH AUTOMATIC UNITS
POWDER (GAS) FIRE EXTINGUISHING
1 Before starting work, the employee must:
1.1 Approaching the door, pay attention to the presence or absence of above front door light signal "Powder (Gas) - do not enter!".
1.1.1 No signal - switch the unit from automatic mode to automatic mode disabled (see the unit operating instructions).
1.1.2 Enter the premises and start work.
1.2 The signal is on - without entering the room, immediately inform the security personnel, the person in charge or the duty officer for the operation of engineering systems, personally or by phone.
2 During operation.
2.1 The first person who detects a fire or signs of combustion (flame, burning, burning smell) is obliged.
2.1.1 Immediately inform the security officer on duty on the internal phone and the city phone number "01" or "112" for the fire guard, indicate the address of the facility, the place where the fire occurred and give your name.
2.1.2 Proceed (if possible) to extinguish the fire with a portable fire extinguisher.
2.1.3 If it is impossible to extinguish the fire with a portable fire extinguisher, immediately leave the premises.
2.2 If the sound and light signaling“Powder (Gas) - go away!”, The employee is obliged to close windows, doors and leave the premises within no more than 30 seconds.
2.2.1 Make sure that all workers have left the premises.
2.2.2 Close the front door tightly.
2.2.3 Break the seal on the PDP (Remote start). Activate the fire extinguishing system by launching the "START" button.
3 At the end of the working day, the employee who closes the premises is obliged:
3.1 Check if the windows are closed; turn off the lights; leave the room and close the front door tightly.
3.2 Transfer the installation to "automatic mode".
3.3 Make sure that the unit is in "automatic mode".
4 Procedure for switching on the unit with a manual call point or with a PDP (Remote start panel).
4.1 The first person who detects a fire or signs of combustion (flame, burning, burning smell) is obliged.
4.2 Check if the windows are closed and if all workers have left the premises.
4.3 Leave the room and close the front door tightly.
4.4 Pull the lever of the manual call point protective glass and press the button) or RAP. After 30 seconds, a gas (powder) fire extinguishing composition will be released into the room.
5 Safety requirements.
5.1 It is allowed to enter the protected area after the release of the extinguishing agent into it and the extinguishing of the fire until the end of ventilation is allowed only in insulating respiratory protection.
5.2 Entering the room without insulating respiratory protection is allowed only after the combustion products have been removed and the gas extinguishing agent has decomposed or the powder dust has settled to a safe level.
5.3 ATTENTION! All signals and actions of the operational duty officer (security service) must be recorded in the technical condition log of the installation. fire automatics with indication of time, date, full name and signature. In the event of a fire detection, actuation of fire automatics or detection of any malfunction of fire automatics, the duty personnel (security services, dispatcher) must immediately report:
- responsible for the operation of engineering equipment and fire-fighting systems.
RUSSIAN JOINT STOCKSOCIETYENERGY
ANDELECTRIFICATIONS «
EECRUSSIA»
DEPARTMENTSCIENCESANDTECHNIQUES
TYPICALINSTRUCTIONS
ONOPERATIONAUTOMATIC
INSTALLATIONSWATERFIRE FIGHTING
RD 34.49.501-95
ORGRES
Moscow 1996
Designed by Joint-stock company "Firm for adjustment, improvement of technology and operation of power plants and networks" ORGRES ".
Performers YES. A. N. ZAMYSLOV Ivanov, A.S. V. M. KOZLOV STARIKOV
Agreed with the Department of the General Inspection for the Operation of Power Plants and Grids of RAO "UES of Russia" on December 28, 1995
Head N.F. Gorev
Head A.P. BERSENEV
STANDARD OPERATING INSTRUCTIONS FOR AUTOMATIC WATER EXTINGUISHING UNITS |
RD 34.49.501-95 |
Expiration date set
from 01.01.97
In the present Typical instructions the basic requirements for the operation of the technological equipment of water fire extinguishing installations used at energy enterprises are given, and the procedure for flushing and pressure testing of pipelines of fire extinguishing installations is also outlined. The scope and sequence of monitoring the state of technological equipment, the timing of the audit of all equipment of fire extinguishing installations are indicated, and basic recommendations for troubleshooting are given.
Responsibility for the operation of fire extinguishing installations has been established, the necessary working documentation and requirements for personnel training have been provided.
The main safety requirements for the operation of fire extinguishing installations are indicated.
The forms of acts of flushing and pressure testing of pipelines and conducting fire tests are given.
With the release of this Model Instruction, the “Typical instruction for the operation of automatic fire extinguishing installations: TI 34-00-046-85” (Moscow: SPO Soyuztekhenergo, 1985) is no longer valid.
1. INTRODUCTION
1.1. The standard instruction establishes the requirements for the operation of technological equipment for water fire extinguishing installations and is mandatory for managers of power companies, shop managers and persons appointed responsible for the operation of fire extinguishing installations.
1.2. Technical requirements for the operation of technological equipment of installations foam fire extinguishing are set out in the "Instructions for the operation of fire extinguishing installations using air-mechanical foam" (Moscow: SPO ORGRES, 1997).
1.3. When operating a fire alarm of an automatic fire extinguishing system (AUP), one should be guided by the "Standard instruction for the operation of automatic fire alarm systems at power enterprises" (Moscow: SPO ORGRES, 1996).
The following abbreviations are adopted in this Model Instructions.
UVP - installation of water fire extinguishing,
AUP - automatic fire extinguishing installation,
AUVP - automatic water fire extinguishing installation,
PPS - fire alarm panel,
PUEZ - control panel for electric valves,
PUPN - fire pump control panel,
PI - fire detector,
PN - fire pump,
OK - check valve,
DV - water drencher,
DVM - modernized water drencher,
OPDR - foam-drencher sprinkler.
2. GENERAL INSTRUCTIONS
2.1. Based on this Model Instruction, the organization that performed the adjustment of the AUP technological equipment, together with the power company where this equipment is installed, must develop a local operating manual for the technological equipment and AUP devices. If the adjustment was carried out by an energy enterprise, then the instructions are developed by the personnel of this enterprise. The local instruction must be developed at least one month before the AUP is put into operation.
2.2. The local instructions must take into account the requirements of this Model instruction and the requirements of factory passports and instructions for the operation of equipment, instruments and apparatus that are part of the AUVP. Reduction of the requirements set forth in these documents is not allowed.
2.3. The local instruction must be revised at least once every three years and every time after the reconstruction of the AUP or in case of a change in operating conditions.
2.4. Acceptance of AUP into operation should be carried out by representatives of:
energy companies (chairman);
design, installation and commissioning organizations;
state fire supervision.
The commission's work program and acceptance certificate must be approved by the chief technical manager of the enterprise.
3. SAFETY MEASURES
3.1. When operating the technological equipment of water fire extinguishing installations, the personnel of power companies must comply with the relevant safety requirements specified in the PTE, PTB, as well as in the factory passports and operating instructions for specific equipment.
3.2. During the maintenance and repair of the AUP, when visiting the premises protected by the AUP, the automatic control of a particular distribution pipeline in this direction should be switched to manual (remote) until the last person leaves the room.
3.3. Pressure testing of pipelines with water should be carried out only according to an approved program, which should include measures to ensure the protection of personnel from a possible rupture of pipelines. It is necessary to provide complete removal air from pipelines. It is prohibited to combine crimping work with other work in the same room. If the pressure testing is carried out by contractors, then the work is carried out according to the permit. The performance of these works by the operational or repair personnel of the power company is documented in a written order.
3.4. Before starting work, personnel involved in pressure testing must be instructed in workplace safety.
3.5. During crimping, no unauthorized persons should be in the room. Pressure testing must be carried out under the supervision of a responsible person.
3.6. Repair work on the technological equipment should be carried out after the pressure is removed from this equipment and the preparation of the necessary organizational and technical measures established by the existing PTB.
4. PREPARATION FOR WORK AND CHECKING THE TECHNICAL CONDITION OF THE FIRE EXTINGUISHING UNIT
4.1. The water fire extinguishing installation consists of:
source of water supply (reservoir, reservoir, city water supply, etc.);
fire pumps (designed for the intake and supply of water to pressure pipelines);
suction pipelines (connecting the water source with fire pumps);
pressure pipelines (from the pump to the control unit);
distribution pipelines (laid within the protected premises);
control units installed at the end of pressure pipelines;
sprinklers.
In addition to the above, based on design solutions, the following can be included in the fire extinguishing installations scheme:
water tank for filling fire pumps;
pneumatic tank for maintaining constant pressure in the network of the fire extinguishing installation;
a compressor for feeding the pneumatic tank with air;
drain taps;
check valves;
dosage washers;
pressure switch;
manometers;
vacuum gauges;
level gauges for measuring the level in tanks and a pneumatic tank;
other signaling, control and automation devices.
The schematic diagram of the water fire extinguishing installation is shown in the figure.
4.2. After the completion of the installation work, the suction, pressure and distribution pipelines must be flushed and subjected to hydraulic tests. The results of flushing and pressure testing must be documented in acts (attachments and).
If possible, the effectiveness of the fire extinguishing installation should be checked by organizing the extinguishing of an artificial fire source (appendix).
4.3. When flushing pipelines, water should be supplied from their ends towards the control units (in order to prevent clogging of pipes with a smaller diameter) at a speed 15 - 20% higher than the speed of water in a fire (determined by calculation or recommendations of design organizations). Flushing should be continued until clean water is consistently produced.
If it is impossible to flush individual sections of pipelines, it is allowed to blow them with dry, clean, compressed air or inert gas.
Schematic diagram of a water fire extinguishing installation:
1 - water storage tank; 2 - fire pump (PN) with electric drive; 3 - pressure pipeline; 4 - suction pipeline; 5 - distribution pipeline; 6 - fire detector (PI); 7 - control unit; 8 - manometer; 9 - check valve (OK)
Note. The standby fire pump with fittings is not shown.
4.4. Hydraulic testing of pipelines must be carried out under a pressure equal to 1.25 working pressure (P), but not less than P + 0.3 MPa, for 10 minutes.
To disconnect the tested section from the rest of the network, it is necessary to install blind flanges or plugs. It is not allowed to use existing control units, repair valves, etc. for this purpose.
After 10 minutes of testing, the pressure should be gradually reduced to working pressure and a thorough inspection of all welded joints and adjacent areas should be performed.
The pipeline network is considered to have passed the hydraulic test if no signs of rupture, leaks and drops in welded joints and on the base metal, visible permanent deformations are found.
The pressure should be measured with two pressure gauges.
4.5. Flushing and hydraulic testing of pipelines should be carried out under conditions that exclude their freezing.
It is prohibited to backfill open trenches with pipelines exposed to severe frosts, or backfill such trenches with frozen soil.
4.6. Automatic water fire extinguishing installations must operate in the automatic start mode. For the period when personnel are in cable facilities (bypass, repair work, etc.), the start-up of installations should be switched to manual (remote) switching (p.).
5. MAINTENANCE OF FIRE EXTINGUISHING UNITS
5.1 ... Organizational activities
5.1.1. Persons responsible for the operation, overhaul and current repairs of the technological equipment of the fire extinguishing installation are appointed by the head of the energy company, who also approves the schedules for technical supervision and equipment repair.
5.1.2. The person responsible for the constant readiness of the technological equipment of the fire extinguishing installation must know well the principle of the device and the procedure for the operation of this equipment, and also have the following documentation:
project with changes made during the installation and commissioning of the fire extinguishing installation;
factory passports and operating instructions for equipment and devices;
this Model Instruction and local operating instructions for process equipment;
acts and protocols of installation and commissioning works, as well as testing of technological equipment;
schedules of maintenance and repair of technological equipment;
"Log book for the maintenance and repair of the fire extinguishing installation."
5.1.3. Any deviations from the scheme adopted by the project, replacement of equipment, additional installation sprinklers or their replacement by sprinklers with a large nozzle diameter must be previously agreed with the design institute - the author of the project.
5.1.4. To monitor the technical condition of the technological equipment of the fire extinguishing installation, a "Register of maintenance and repair of the fire extinguishing installation" should be kept, which should record the date and time of the inspection, who carried out the inspection, the detected faults, their nature and time of their elimination, the time of forced shutdown and activation fire extinguishing installations, carried out by testing the operation of the entire installation or individual equipment. The approximate form of the journal is given in the appendix.
At least once a quarter, the chief technical manager of the enterprise must familiarize himself with the contents of the journal on receipt.
5.1.5. To check the readiness and efficiency of the AUVP, a complete audit of the technological equipment of this installation should be carried out once every three years.
During the audit, in addition to the main work, pressure testing of the pressure pipeline is carried out and flushing (or purging) and pressure testing of distribution pipelines (pp. -) are carried out in two or three directions, which are in the most aggressive environment (dampness, gas pollution, dust).
If deficiencies are found, it is necessary to develop measures to ensure their complete elimination in a short time.
5.1.6. An automatic fire extinguishing installation in accordance with the schedule approved by the head of the relevant workshop, but at least once every three years, must be tested (tested) according to a specially developed program with the actual start-up of them, provided that this does not entail a shutdown of the technological equipment or all the production process. During testing on the first and last sprinklers, the water pressure and irrigation intensity should be checked.
Testing should be carried out for 1.5 - 2 minutes with the inclusion of serviceable drainage devices.
Based on the results of testing, an act or protocol must be drawn up, and the fact of testing itself must be registered in the "Journal of maintenance and repair of the fire extinguishing installation".
5.1.7. Checking the operation of AUVP or certain types of equipment should be carried out during the withdrawal for repair, maintenance of the protected premises and the technological unit.
5.1.8. For storage of spare equipment, equipment parts, as well as fixtures, tools, materials, devices necessary for the control and organization of repair work of AUVP, a special room should be allocated.
5.1.9. The technical capabilities of AUVP should be included in the operational plan for extinguishing a fire at a given power plant. During firefighting trainings, it is necessary to expand the circle of personnel who know the purpose and device of the AUVP, as well as the procedure for activating it.
5.1.10. The personnel servicing the AUVP compressors and pneumatic tanks must be trained and certified in accordance with the requirements of the Gosgortekhnadzor rules.
5.1.11. The person responsible for the operation of the technological equipment of the fire extinguishing installation must organize training with personnel assigned to control the operation and maintenance of this equipment.
5.1.12. In room pumping station AUVP should be posted: instructions on how to turn on the pumps and open valves, as well as conceptual and technological diagrams.
5.2 ... Technical requirements for AUVP
5.2.1. The entrances to the building (room) of the pumping station and the fire extinguishing installation, as well as the approaches to the pumps, pneumatic tank, compressor, control units, pressure gauges and other equipment of the fire extinguishing installation, must always be free.
5.2.2. On an operating fire extinguishing installation, the following must be sealed in working position:
hatches of reservoirs and tanks for storing water supplies;
control units, gate valves and manual cranes;
pressure switch;
drain taps.
5.2.3. After the fire extinguishing installation has been triggered, its operability must be fully restored no later than 24 hours later.
5.3 ... Water storage tanks
5.3.1. Checking the water level in the tank should be carried out daily with registration in the "Log book of maintenance and repair of the fire extinguishing installation".
If the water level drops due to vapors, it is necessary to add water, if there are leaks, locate the damage to the reservoir and repair the leaks.
5.3.2. The correct operation of the automatic level gauge in the tank should be checked at least once every three months at positive temperatures, monthly - at negative temperatures and immediately in case of doubts about the correct operation of the level gauge.
5.3.3. The tanks must be closed for unauthorized access and sealed, the integrity of the seal is checked during the inspection of the equipment, but at least once a quarter.
5.3.4. The water in the tank should not contain mechanical impurities that could clog pipelines, metering washers and sprinklers.
5.3.5. To prevent decay and blooming of water, it is recommended to disinfect it with bleach at the rate of 100 g of lime per 1 m3 of water.
5.3.6. It is necessary to change the water in the tank annually in the fall. When changing the water, the bottom and inner walls of the tank are cleaned of dirt and build-up, the damaged paint is restored or completely renewed.
5.3.7. Before the onset of frost near buried tanks, the gap between the upper and lower hatch covers must be filled with insulating material.
5.4 ... Suction pipeline
5.4.1. Once a quarter, the condition of the bushings, shut-off valves, measuring instruments and the water intake well is checked.
5.4.2. Before the onset of frost, the fittings in the water intake well must be inspected, repaired if necessary, and the well must be insulated.
5.5 ... Pumping station
5.5.1. Before testing the pumps it is necessary to check: the tightening of the oil seals; the level of lubrication in the bearing tubs; correct tightening of foundation bolts, pump cover nuts and bearings; suction-side piping connections and the pumps themselves.
5.5.2. Once a month, pumps and other equipment of the pumping station should be inspected, cleaned of dust and dirt.
5.5.3. Each fire pump must be turned on at least twice a month to create the required pressure, which is recorded in the operational log.
5.5.4. At least once a month, the reliability of the transfer of all fire pumps to the main and reserve power supply should be checked with the registration of the results in the operational log.
5.5.5. If there is a special tank for filling the pumps with water, the latter must be inspected and painted annually.
5.5.6. Once every three years, pumps and motors according to p. of this Model Instruction must undergo an audit, during which all existing deficiencies are eliminated.
Repair and replacement of worn out parts, check of oil seals are carried out as needed.
5.5.7. The pumping station must be kept clean. In the absence of duty, it must be locked. One of the spare keys must be kept on the control panel, which must be indicated on the door.
5.6 ... Pressure and distribution pipelines
5.6.1. Once a quarter, it is necessary to check:
absence of leaks and deflections of pipelines;
the presence of a constant slope (not less than 0.01 for pipes with a diameter of up to 50 mm and 0.005 for pipes with a diameter of 50 mm and more);
condition of pipeline fasteners;
lack of contact with electric wires and cables;
condition of painting, absence of dirt and dust.
Discovered deficiencies that could affect the reliability of the installation should be eliminated immediately.
5.6.2. The pressure pipeline must be always ready for action, i.e. filled with water and under operating pressure.
5.7 ... Control units and valves
5.7.1. For AUVP transformers and cable structures in locking and starting devices, steel reinforcement electrified gate valves with automatic start of grade 30s 941nzh should be used; 30s 986nzh; 30s 996nzh with a working pressure of 1.6 MPa, repair valves with a manual drive brand 30s 41nzh with a working pressure of 1.6 MPa.
5.7.2. The state of the control units and valves, the presence of a seal, the pressure values before and after the control units must be monitored at least once a month.
5.7.3. An inspection should be carried out once every six months electrical circuit actuation of the control unit with its automatic activation from the fire detector when the valve is closed.
5.7.4. The installation site of the control unit should be well lit, inscriptions on pipelines or special stencils (unit number, protected area, type of sprinklers and their number) should be made with indelible bright paint and clearly visible.
5.7.5. Any damage to valves, valves and non-return valves that could affect the reliability of the fire extinguishing installation must be repaired immediately.
5.8 ... Sprinklers
5.8.1. As water sprinklers for automatic fire extinguishing of transformers, sprinklers OPDR-15 are used with a working water pressure in front of the sprinklers in the range of 0.2 - 0.6 MPa; for automatic fire extinguishing of cable structures, sprinklers DV, DVM with a working pressure of 0.2 - 0.4 MPa are used.
5.8.2. When inspecting switchgear equipment, but at least once a month, the sprinklers must be inspected and cleaned of dust and dirt. If a malfunction or corrosion is detected, measures must be taken to eliminate them.
5.8.3. During repair work, sprinklers must be protected from plaster and paint (for example, plastic or paper caps, etc.). Traces of paint and mortar found after repair must be removed.
5.8.5. To replace faulty or damaged sprinklers, a reserve of 10-15% of the total number of installed sprinklers must be created.
5.9 ... Pneumatic tank and compressor
5.9.1. The inclusion of the pneumatic tank in operation should be carried out in the following sequence:
fill the pneumatic tank with water to about 50% of its volume (control the level on the water gauge glass);
turn on the compressor or open the valve on the compressed air line;
raise the pressure in the pneumatic tank to the working pressure (controlled by the pressure gauge), then connect the pneumatic tank to the pressure pipeline, creating a working pressure in it.
5.9.2. An external inspection of the pneumatic tank should be carried out daily, check the water level and air pressure in the pneumatic tank. When the air pressure drops by 0.05 MPa (in relation to the working one), it is pumped up.
The compressor is tested at idle speed once a week.
5.9.3. Maintenance of the pneumatic tank and compressor, carried out once a year, includes:
emptying, inspecting and cleaning the pneumatic tank:
removal and check at the stand safety valve(in case of malfunction, replace with a new one);
painting of the surface of the pneumatic tank (indicate the date of repair on the surface);
detailed inspection of the compressor (replace worn parts and fittings);
fulfillment of all other technical requirements stipulated by the factory passports and operating instructions for the pneumatic tank and compressor.
5.9.4. It is prohibited to turn off the pneumatic tank from the fire extinguishing installation diagram.
5.9.5. The inspection of the pneumatic tank is carried out by a special commission with the participation of representatives of the Gosgortekhnadzor, local authorities of the State Fire Supervision and this energy company.
Note. The compressor should only be started up manually. In this case, it is necessary to monitor the level in the pneumatic tank, since when automatic switching on compressor, it is possible for air to squeeze out water from the pneumatic tank and even from the network.
5.10 ... Pressure gauges
5.10.1. The correctness of the readings of the pressure gauges installed on the pneumatic tanks should be checked once a month, installed on the pipelines - once every six months.
5.10.2. Full check at the fire extinguishing installation, all pressure gauges with their sealing or stamping must be carried out annually in accordance with the current regulation.
6. ORGANIZATION AND REQUIREMENTS FOR REPAIR WORKS
6.1. During the repair of the technological equipment of the fire extinguishing installation, one should, first of all, be guided by the requirements of the passport, the instructions of the plant for the operation of specific equipment, the requirements of the relevant standards and technical conditions, as well as the requirements of this Model Instruction.
6.2. When replacing a section of a pipeline on a bend, the minimum radius of the inner bend curve steel pipes when bending them in a cold state, it should be at least four outer diameters, in a hot state - at least three.
The bent part of the pipe must be free of folds, cracks or other defects. Ovality at bending points is allowed no more than 10% (determined by the ratio of the difference between the largest and smallest outer diameters of the bent pipe to the outer diameter of the pipe before the bend).
6.3. The difference in wall thickness and displacement of the edges of abutting pipes and pipeline parts should not exceed 10% of the wall thickness and should not be more than 3 mm.
6.4. Before welding, the edges of the pipe ends to be welded and the surfaces adjacent to them must be cleaned of rust and dirt to a width of at least 20 mm.
6.5. Welding of each joint must be performed without interruption until the entire joint is fully welded.
6.6. The welded joint of pipes should be rejected if the following defects are found:
cracks emerging on the surface of the seam or base metal in the welding zone;
sagging or undercuts in the zone of transition from base metal to deposited metal;
burn-throughs;
unevenness of the weld in width and height, as well as its deviations from the axis.
6.7. In especially damp rooms with a chemically active environment, the pipe fastening structures must be made of steel profiles with a thickness of at least 4 mm. Pipelines and fastening structures must be coated with protective varnish or paint.
6.8. Pipeline connections for open installation should be located outside walls, partitions, ceilings and other building structures of buildings.
6.9. Fastening of pipelines to building structures of buildings should be carried out with normalized supports and hangers. Welding of pipelines directly to metal structures buildings and structures, as well as elements of technological equipment are not allowed.
6.10. Welding of supports and hangers to building structures should be carried out without weakening their mechanical strength.
6.11. Sagging and bending of pipelines are not allowed.
6.12. Each pipe bend over 0.5 m in length must be secured. The distance from the hangers to the welded and threaded pipe joints must be at least 100 mm.
6.13. Newly installed sprinklers must be cleaned of preservative grease and checked with a hydraulic pressure of 1.25 MPa (12.5 kgf / cm2) for 1 minute.
The average service life of sprinklers is determined at least 10 years.
6.14. The performance of the sprinklers DV, DVM and OPDR-15 is given in table. ...
Table 1
Outlet diameter, mm |
Sprinkler capacity, l / s, at pressure MPa |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
DV-10 and DVM-10 |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
table 2
The main governing document when developing measures for the operation of APPZ installations are: PPB RB 1.02-94 "Industrial safety rules for the operation of technical means of fire protection". The list of organizational measures, first of all, includes the development of documentation at the protected object that determines the procedure for the operation of APPS facilities, functional responsibilities maintenance and operational personnel, as well as the organization of control over their implementation. The complex of organizational measures also includes the development and maintenance of operational documentation for the funds of the APPZ. The facility must have the following documentation: design documentation and as-built drawings for the installation; certificate of acceptance and commissioning of the installation; passports for equipment and devices; list of mounted equipment, assemblies, instruments and automation equipment; installation operating instructions; a list of regulated works on the maintenance of installations; maintenance schedule; register of works on maintenance and repair of installations; duty schedule of operational (duty) personnel; a log of the delivery and acceptance of duty by operational personnel; plant malfunction log; job descriptions. By order of the head of the facility, the following must be appointed: the person responsible for the operation of the UPA; service personnel for the maintenance of the UPA; operational (duty personnel) The person responsible for the operation of the UPA is obliged to ensure: maintaining the UPA in working order - performing maintenance daily, weekly, monthly, once every 3 months, once every six months, once a year, once every 3.5 years; control over timely and high-quality service and scheduled preventive maintenance; training of service and operational personnel and systematic control over the development, maintenance of operational documentation; informing about cases of triggering; General rules for technical content The operating conditions of automatic water and foam fire extinguishing installations must meet the requirements of GOST 12.4.009-83, PPB of the Republic of Belarus when operating technical means of fire protection, technical specifications equipment. During the operation of the installations, the presence of the required water pressure in the systems of the main water supply is monitored. as well as for the presence of a standard reserve of a foaming agent or a foaming agent solution in spare tanks of foam fire extinguishing installations. In the premises of the oil storage, the air temperature must be at least 5 ° C and not more than 20 ° C. The floors, stairs and platforms of the station premises of fire extinguishing installations should be kept clean and serviceable. The keys to the station room must be kept by the personnel on duty. When caring for automatic water feeders, it is necessary to monitor the level and purity of the water in the water tank or hydraulic tank. In areas with a harsh climate, the presence and condition of heating of water-pressure and hydropneumatic tanks is monitored. In hydropneumatic installations, the air pressure in the system and the water level are monitored. When starting the compressor, you must first make sure that it is working properly. During trial tests of the compressor Special attention refers to the temperature of the lubricating oil, bearings and other rubbing joints. Due to the high corrosiveness of some types of foaming agents, additional monitoring of the good condition requires devices for preparing a foaming solution. After testing the functionality, or after extinguishing the fire, the metering devices of the foam fire extinguishing installations are thoroughly rinsed with clean water. During operation, the control panel is constantly inspected (the state of the relay, input starters, buttons, switches). Unarmoured cables. inserted into small-sized shields, from below are protected from mechanical damage. Monitoring of the serviceability of the light and sound signaling about the presence of voltage on the feeders and about the disappearance of voltage on the control and signaling circuit boards is carried out. Fire extinguishing installations start devices are sealed and protected from accidental start-up and mechanical damage. At each control unit, signs are posted indicating the name of the protected premises, the type and number of sprinklers in the section. In air systems, the air pressure should be 25% of the water pressure. In water systems, the pressure above the control and signal valve (KSK) should not exceed the pressure under the KSK in the presence of an automatic pump by 0.05 MPa (0.5 kgf / cm "), in other cases - by 0.03 MPa (0.3 kgf / cm2) The main gate valve in front of KSK, KGD, taps on the stimulating pipeline, taps to pressure gauges, valves of the dosing device (foam installations) are constantly kept open. Not allowed: use of pipes of fire extinguishing installations for suspension or fastening of any equipment; connection of production equipment and sanitary devices to feed pipelines; installation of shut-off valves and flange connections on supply and distribution pipelines, as well as the use of internal fire hydrants installed on the sprinkler network for other purposes, except for extinguishing fires. Sprinklers for fire extinguishing installations must be kept clean. As the main water supply, water pipelines are used, which provide the water flow and pressure necessary for fire extinguishing, as well as booster pumps. If there is insufficient pressure in the water supply system used to power the sprinkler installation, then booster pumps are provided. At least two pumps are installed in the pumping station - a working one and a standby one. The power supply of the pump motors is provided from two independent sources. If there is only one power source, then the backup pump is driven by an internal combustion engine. manually activated. The electric control of the pumping station is carried out in such a way that it is possible to manually turn on the pump motors from the pumping station premises. Remote start is allowed by means of buttons installed in the premises of the fire station and near the internal fire hydrants. The pumping station room is provided with telephone communication with the dispatch center and emergency lighting. At the entrance to the pumping station premises, a sign is posted and a light board "Fire extinguishing station" is installed. In the room of the pumping station, a piping diagram of the pumping station and a schematic diagram of the installation are posted. The room is kept permanently locked, the keys are kept by the staff on duty. Automatic volumetric fire extinguishing installations with an electrical part and designed to protect premises with people staying in them are allowed for commissioning if they include: devices for switching automatic start-up to manual with the issuance of a corresponding signal to the premises of the personnel on duty; sound and light fire alarms. A light warning signal in the form of an inscription on the light boards "Foam - go away" and an audible warning signal must be issued simultaneously within the protected premises. In this case, a light signal "Foam - do not enter" should appear at the entrance to the protected room, and in the room of the duty personnel - a corresponding signal with information about the supply extinguishing agent. Automatic fire extinguishing installations, the design of which provides for the presence of a duplicate manual start, must be operated in automatic mode. Devices for manual start-up of volumetric (except for local) fire extinguishing installations should be located outside the protected area near emergency exits with free access to them. Manual start devices for local fire extinguishing installations should be located outside the possible combustion zone at a safe distance from it. In this case, it should be possible to remotely switch on the unit outside the protected room. Maintenance of water and foam fire extinguishing installations The efficiency of installations depends on the quality of their operation, especially on the correct maintenance (MOT). Maintenance of water installations includes a number of activities carried out daily, weekly, monthly, once every 3 months, once every 6 months, annually, once every 3 years and once every 3.5 years. Daily maintenance includes the following operations: a) checking the cleanliness and order in the premises of the fire extinguishing station; b) control of the water level in the tank using control and measuring devices; c) external examination pulse device or pneumatic tank and control of the water level and air pressure (when the pressure drops by 0.05 MPa (0.5 kgf / cm "), air should be pumped); d) checking the voltage at the power supply inputs; e) external inspection of control units and control of pressure above and below valve (according to pressure gauges); f) control of access to control units and manual cranes, as well as control over the observance of the minimum distances from the sprinklers to the stored materials (which must be at least 0.9 m). Weekly maintenance includes all daily maintenance work and the following operations: a) control of pumps of fire extinguishing stations: starting pumps at 10, checking the serviceability of instrumentation (gearbox) and the tightness of fittings and connections, renewing the supply of lubricant in the lubricators, testing the compressor at idle, checking the automatic pump activation with switching the power supply from the working input to the reserve one ; b) check of control units (cleaning of taps with a small hole, check of operation of control units); c) checking the presence of spare sprinklers in the control cabinet: d) control of the pipeline system (inspection for the purpose of detecting and eliminating leaks, checking the condition of fasteners and painting of pipelines, tightness of stop valves, testing of manual valves); e) cleaning of sprinklers and stimulators from dust in dusty rooms. Monthly maintenance includes the following works: a) carrying out activities for weekly maintenance: b) cleaning the surface of pipelines from dust and dirt: c) replenishment of reservoirs with water when the level drops below the design mark: d) tightening of nuts on flange connections of pump nozzles with pipelines and foundation bolts and other preventive work: e) checking the serviceability of the pressure gauges of the pneumatic tank by comparison with the control pressure gauge; f) checking the operation of the installation in manual and automatic modes (if there are no specially trained personnel at the facilities). THAT, carried out every 3 months. includes: a) carrying out activities for monthly maintenance; b) checking the internal fire hydrants located on the sprinkler network (by opening them); c) change of pump oil seal packings: d) flushing and lubricating pump bearings: e) replacement of the stuffing box seals of the compressor; f) checking the operation of the installation in manual and automatic modes (if the facility has specially trained personnel). Annual maintenance includes the following works: a) metrological check of the checkpoint; b) control of the equipment of the fire extinguishing station (inspection and cleaning of the pneumatic tank at the stand; painting the outer surface of the impulse device of the pneumatic tank; cleaning, inspecting and repairing the compressor and fittings; cleaning, repairing and painting the inner and outer surfaces of the pump priming tank: testing the tightness of check valves and gate valves); c) measurement of working resistance and cleaning and repair of control units with replacement of faulty parts, rubber diaphragms and gaskets; d) bulkhead seals of all valves: e) flushing pipelines and changing water in the installation and the tank. Insulation resistance electrical circuits measured every 3 goals during the next annual maintenance. Maintenance, carried out once every 3.5 years, includes the following works: a) disassembly, cleaning of pumps and their fittings, detailed inspection of all parts, repair and replacement of faulty ones: b) hydraulic and pneumatic tests of the pipeline network; c) cleaning of tanks, repair of the waterproofing layer and inlet valves: d) flushing and cleaning of pipelines from dirt and rust with replacement of faulty fasteners; e) painting of pipelines after flushing and cleaning. The specificity of the operation of foam fire extinguishing installations (SCP) is determined by the presence of a foam concentrate or a foam-forming solution in the tanks of the installation, the design of the dosing device and the foam generator (sprinkler). The quality of foaming agents and foaming solutions filled in the UPP is checked at least once a quarter in accordance with the "Instructions for use, storage, transportation and quality control of foaming agents"). Foaming agents are considered unsuitable if the values of their indicators are 20% lower than the normative ones. Defective foaming agents are written off and used either for educational purposes or as wetting additives to water. If the foaming solution or foaming agent is stored in a reinforced concrete tank, then at least once every 3 years the waterproofing layer of the tank is checked and, if necessary, repaired in order to avoid leakage of the extinguishing agent. During the operation of the soft starter, special attention should be paid to the state of foam generators (in particular, mesh), containers with a foam concentrate and communications for its supply, due to the fact that some constituent parts of foam concentrates tend to crystallize, as a result of which the flow cross-sections of pipes, branch pipes, taps may be clogged. During the operation of equipment for protecting tanks with flammable liquids, the condition of the sensors for detecting fire (sprinklers or TRV-2 detectors) installed in the upper part of the tank and the foam chamber (especially its sealing gate) is also checked. After the operation of the UPP of its communication, the elements are washed with water. Periodic maintenance of foam fire extinguishing installations is performed in the same sequence as for water fire extinguishing installations. With the exception of the following work performed monthly: in containers where the foam concentrate or its solution is stored, the safety of the seals on the inspection hatches is checked: if the seals are torn off, the frother or solution is sent for analysis, and the hatches are sealed again; include on a short time dosing devices (for flushing with clean water); the pumps are stirred with a foaming solution or a foaming agent. Once every 3 years, the performance of the soft starter is selectively checked. The procedure for accepting duty An interceding employee from among the personnel on duty must arrive 15 minutes before the start of duty to the person responsible for the operation of the APPZ facilities for briefing. The changing staff on duty is obliged to: put in order workplace: fill out the register of reception and delivery of duty, conduct a review of the equipment together with the intervening duty officer. During the acceptance of duty, an employee from among the operational personnel is obliged to accept service and technical documentation. Check the operability of telephone communication with the Ministry of Emergency Situations, other services of the facility. In case of any malfunctions, make a note in the fault log and inform the person in charge of the operation to take corrective measures. Report the change of duty and malfunctions to the person in charge of the operation of the SPS. Actions of operating personnel when the control equipment is triggered. While on duty, the operating personnel is obliged to monitor the technical condition of the UPA. In cases of AUPT triggering, record it in the triggering log. At each trigger, inspect the room together with the instructors of the safety department and give an opinion on a false alarm. leaving on official matters, leave the power engineer on duty for himself, indicating his location. In the event of a fire, operating personnel must: Call the units of the Ministry of Emergency Situations; Notify people in the building about the fire; Inform the management of the organization about the fire; Start extinguishing the fire using primary fire extinguishing equipment. (in the presence of AUPT - check the inclusion of AUPT, if necessary, turn it on manually). Instructions for service personnel. Service personnel are obliged to: check the cleanliness and order of the PT station; conduct an external examination of the incentive system; conduct an external inspection of the UU and control the pressure above and below the valve (not a pressure gauge); control access to the control device and manual cranes, compliance with the minimum distances from the sprinklers to the stored materials; control the serviceability of the pumps of the PT station; check the serviceability of the control unit. I APPROVE: INSTRUCTIONS _________________ 1. AUTOMATION OF FIRE EXTINGUISHING. For fire extinguishing are provided: 2. AUTOMATIC FIRE ALARMS AND SOUE Instructions for the actions of the personnel on duty when a fire alarm or malfunction is triggered Upon receipt of the "FAILURE" signal on the "Z-101" fire alarm panel (an intermittent fault signal is sent to the built-in sounder and turns on the LED indicators on the front panel of the device): 3. SMOKE EXHAUST SYSTEM The instruction was made by ____________________ ANNEX 1. APPENDIX 2. 5. Acceptance-handover of duty and technical condition of the system: 6.Accounting for failures and malfunctions of fire automation systems 7. Accounting for technical maintenance and scheduled preventive maintenance of fire automation systems. 8. Testing the knowledge of personnel serving fire automation systems 9.Accounting the operation (shutdown) of fire automation systems and information from the GPN bodies 10. Briefing of technical and operational personnel on safety measures when working with fire automation systems. APPENDIX 3. 9.Saved material assets due to the presence and timely operation of the fire automation system _____________________________________________ ______________________________________________________________________ ((name, signature of the official) "_________" _________________________ 20_____ APPENDIX 4. Regulations Regulations Download the operating instructions for the fire automatics General Provisions The procedure for the operation and maintenance of automatic fire extinguishing systems (installations) is regulated by GOST, SNiP, PPB, departmental norms and rules, technical operational documentation for installations. For each AFS for the persons responsible for the operation of the installation, and for the personnel serving this installation, operating instructions should be developed taking into account the specifics of the protected premises, approved by the management of the enterprise and agreed with the organization that carries out maintenance and R AUP. The restoration of the operability of the AUP or APSS after all operation or failure should not exceed: Between the operating organization and the enterprise that carries out maintenance and repair, a "Agreement for the maintenance and repair of automatic fire extinguishing installations" must be concluded and valid. For the installation accepted at TO and R, after the conclusion of the contract, the following must be filled in: The enterprise must have the following technical documentation: All the necessary documentation for the AUP (or photocopies) must be kept by the person responsible for the operation of the AUP. Features of checking fire extinguishing installationsChecking water and foam fire extinguishing installations When inspecting the technical condition of water and foam fire extinguishing installations, it is necessary to be guided by GOST R 50680, GOST R 50800, NPB 88-2001 and the requirements of the VNIIPO Methodological Recommendations. When operating the AUP, it is prohibited: Features of checking gas fire extinguishing installations In the process of controlling the UGP during operation, it is necessary: The control and testing of the UGP should be carried out without the release of the fire extinguishing agent according to the methods set forth in GOST R 50969. Features of checking aerosol fire extinguishing installations When examining objects protected by AUP, it is necessary to monitor compliance with a number of regulatory requirements. Features of testing modular powder fire extinguishing installations. The list and frequency of maintenance work is determined in accordance with the regulations drawn up by the MAUPT developer on the basis of the technical documentation for the component parts. The requirements of the maintenance regulations for a specific IAPMT must not be lower than the requirements of the standard maintenance regulations.
Bodies of the State Border Service check for the presence of entries in the register of maintenance work and maintenance MAUPT in accordance with the regulations and checking the maintenance of the passport of the vessel operating under pressure (if necessary, its presence, according to PB 10-115). Additionally, representatives of the State Border Service conduct an external examination of the IAPM: Maintenance of AUP after commissioning should be carried out in the amount and terms established by special schedules, in accordance with technical documentation on its elements, but at least once a quarter. The fire extinguishing installation after replacing the equipment, repairs must undergo 72 hours of control in the operating mode (measures should be taken to exclude the supply of OTS). It is necessary to observe the rules of storage, transportation and disposal of the installation elements specified in the operating documents for these elements. In the protected premises there must be instructions on the actions of the people working in them in the event of the installation being triggered. During the period of repair work in the protected premises sprinklers (sprinklers, nozzles, thermal locks, fire detectors, elements of a cable stimulating system) must be protected from plaster, paint, whitewash, etc. After finishing the repair of the room, the devices that provided protection must be removed. Defective sprinklers and nozzles should be replaced with similar products (for example, from the spare parts kit), while maintaining their orientation in space in accordance with the installation project. It is not allowed to install plugs or plugs instead of faulty sprinklers or nozzles. It is not allowed to clutter up the space in front of the sprinklers (nozzles) with equipment, lighting fixtures, etc. During maintenance, it is necessary to periodically flush (purge) pipelines to remove dirt and rust, as well as test pipelines for strength and tightness. It is prohibited: - use pipelines of the installation for suspension or fastening of any equipment; - connect production equipment and sanitary appliances to the feed (distribution) pipelines of the installation, install shut-off valves on them (except as provided for by the project); - use internal fire hydrants for other purposes than extinguishing fires. When carrying out restoration work paints and varnishes of the installation elements, the identifying colors established by the project should be observed. During the operation of the installation volumetric fire extinguishing type of fire load, dimensions and placement of openings in the protected premises must correspond to the project. Measures should be taken to eliminate technologically unjustified openings, to monitor the performance of door closers, etc. Premises, if necessary, should have serviceable devices (or permanently open openings) to relieve pressure. Changes in the characteristics of the premises that were used as initial data in the design of the AFS (changing the type of fire load, the size and location of permanently open openings, etc.) should be agreed with the AFS developer organization. Fire post must be provided with direct telephone communication with the pumping station (gas fire extinguishing station), as well as city telephone communication, serviceable electric lights. Periodically, the operability of the light and sound signaling about the actuation of the fire extinguishing system and its malfunction should be checked. A round-the-clock and constant duty of personnel should be organized at the fire post. The actions of the personnel on duty upon receipt of signals are stipulated by the instructions. Appendix: Forms of operational documents for automatic fire extinguishing systems (installations) Download the app in Word format >>> Please or to access this content Recommended to read |