Instructions for employees in a room with a PT

1. STANDBY MODE
In standby mode, the unit continuously monitors its performance, recharges the built-in batteries and polls fire detectors. If any malfunction occurs, an intermittent sound signal is turned on, and a signal is transmitted FAILURE.
The device must be in automatic mode at night or when service personnel or customers leave the protected premises. Automatic mode is activated with the button AUTOMATIC ON... after which the indicator lights up in red.
If someone is in the room, then the automatic mode is turned off with the button. AUTOMATIC OFF. after which the indicator lights up in red.

2. MODE ATTENTION
When one fire detector in the fire loop is reset, the indicator lights up ATTENTION, this means that one of the fire detectors has been triggered. It is necessary to go through the premises and find a triggered fire detector.To reset the sound signal, press the button RESET

3. FIRE MODE
When two fire detectors are reset in the fire loop, the siren is activated, the indicator of the corresponding direction blinks red, the indicator starts blinking FIRE the corresponding direction. In addition, a signal is issued to turn on the light and sound annunciator in the corresponding direction "POWDER LEAVE".
Then, in automatic mode, in the appropriate direction, after a delay of 60 seconds (the time can be changed), the fire extinguishing agent launch mode will turn on, the display will turn on "POWDER LEAVE" and the panel "GAS DO NOT ENTER" turns on. During the delayed start time, the fire extinguishing start can be canceled by pressing the button. RESET.
To disable the unauthorized (false triggering of fire detectors) start of the AUP, after making sure that there is no fire, you must press the button RESET... Then by pressing the button AUTOMATIC OFF... bring the indicator to a luminous state.
4 . D Personnel actions in case of activation of the automatic fire extinguishing system
In case of starting the automatic fire extinguishing system, in order to prevent repeated operation of the installation, it is recommended to adhere to the following sequence of actions:
1) Visually assess the situation in the protected room (group of rooms). If possible, determine the reason for starting the system: the presence of fires, smoke, actuation of the remote start button. Acting on the situation, take the necessary measures to protect people and property from fire and exposure to a fire extinguishing agent.
2) If the fire has been extinguished, or the installation has been falsely switched on, turn off the sound signaling by pressing the button

"Sound OFF" ...
3) On the indicators of the front panel of the device, check the presence of a fire alarm (indicators "Attention", "Fire" ), automatic start state (indicator "Automation"), startup mode (indicator "Quenching"). Determine the zones in the mode "Fire".
4) Check the light indication on triggered detectors (if any), check the presence or integrity of safety elements on manual call points.
5) Reset the mode on the device "Quenching" by pressing a button "Extinguishing reset"... Reset mode "Fire" by pressing a button "Fire relief".
6) Record your actions and observation results in the journal. Report the incident ________________________.
7) De-energize the device by disconnecting the main and backup power supplies. De-energize S2000-KPB units (if any).
8) After completing the investigation of the reasons for the operation of the installation, before restoring the power supply to the device, disconnect the automatic fire-fighting modules from the starting circuits of the device and the S2000-KPB units (if any), replacing them with simulators. A fuse can be used as a simulator, the operating current of which corresponds to the operating current of the automatic module.
9) Carry out a set of commissioning works, during which the system operability must be checked.
10) After making sure that the device is not in alarm mode, de-energize it by disconnecting the main and backup power supplies. Replace simulators with working fire modules. Restore the power supply to the device.

Purpose and modes of illumination of indicators on the S2000-ASPT panel

Indicator name

Glow color

Appointment

1. Green
2.3. On in intermittent mode with a frequency of 2 Hz

1. Indication of the standby mode of the device
2. Indication of the "Test" mode
3. Indication of the "Instrument alarm" mode

ATTENTION

Attention mode indication

Red
Intermittent switching

Fire mode indication
"Instrument alarm"

Indication of the AUP start mode

Automatic ON

Indication of the operation of devices in the automatic start-up mode of AUP

Automatic OFF

Indication of the operation of devices in the mode of remote start of AUP

Sound OFF.

Indication of shutdown of external protection zone and internal protection station in the modes "Fire", "Delayed start", "Start AUP", "Fault".

FAILURE

1. Signal circuit malfunction indication
2. Indication of a malfunction of the CO and ZO outputs
3. Indication of a malfunction of the starting circuit
4. Indication of a malfunction of the OP source
5. Indication of malfunction of the RP source
6. Fault indication from the S2000-KPB unit
7. Indication of opening the device case

Developed by OOO Montazhgrad. Copying of the text is allowed only if the authorship is indicated and there is an active link to the site of Montazhgrad LLC

Construction of automatic fire extinguishing systems using S2000-ASPT

S2000-ASPT is a device designed to control autonomous and centralized systems of powder, gas and aerosol fire extinguishing.

To accomplish this task, the device monitors 3 fire alarm loops, from which information about the detection of fire is received. When configuring the control panel, each of the loops is assigned a type, which indicates to the control panel the class and response algorithm of the detectors included in the loop. When a fire signal is received, the S2000-ASPT analyzes the type of detectors in the loop, after which it decides to start extinguishing or acts according to another established algorithm.

If the S2000-ASPT decision is made to start extinguishing, light indicators are turned on, which are usually located inside and outside the room to warn people about the start of extinguishing. Further, the countdown of the start delay begins, after which the extinguishing agent is released. Additionally, a sensor is installed on the door that monitors the door status and can cancel the fire extinguishing start in case of entry / exit from the room. It is also possible to connect a manual start button to start the system locally, and a reader, which allows you to disable the automatic control process. In addition, when the S2000-ASPT operates in a centralized system, the start of extinguishing can be initiated by the network controller.

Basically, the above system algorithm is relevant for all fire extinguishing systems, however, each of them has its own specific features, depending on the principles of operation of each specific system and its configuration. The most common options for fire extinguishing systems using the S2000-ASPT device will be considered further.

Construction of powder (aerosol) fire extinguishing systems using S2000-ASPT

Powder extinguishing installations are the most common due to their simplicity and relatively low cost, as well as the less time required to recover the system after a firing. However, they also have some negative features, the main of which are the danger to humans, damage to the room, and the high laboriousness of cleaning the powder after the system is triggered.

The principle of operation of the installation shown in the diagram is as follows. When a fire signal is received from fire detectors, or the button “start extinguishing” is pressed, the S2000-ASPT device turns on the light indicators “Do not enter powder” / “Powder leave” and sirens, and also starts counting the set delay time for starting extinguishing. If the start is not canceled during this time, the device sends a signal to the S2000-KPB control and launch unit, which activates the fire extinguishing modules. The S2000-KPB is controlled via the RS-485 interface. The start can be canceled automatically, by a signal from the door lock sensor, or manually from the reader connected to the S2000-ASPT.

The construction of a centralized system is distinguished by the presence of several extinguishing zones, the control devices of which are combined with an RS-485 interface with a network controller and other devices located in the fire post or at the guard post. Each of the zones is registered in a separate section in the network controller. Information about the state of each section is transmitted to the S2000-PT indication unit, which provides indication and remote control of fire extinguishing devices.

This system provides 2 levels of control: local control of the S2000-ASPT device; remote control of the S2000M network controller. In this case, even if there are problems with communication via RS-485, extinguishing will be triggered by the S2000-ASPT device without the participation of the network controller. Otherwise, the structure and principle of operation of each individual zone is similar to the operation of the autonomous powder fire extinguishing system described above.

Construction of gas fire extinguishing systems using S2000-ASPT

Gas fire extinguishing systems are less common and, as a rule, are used in certain categories of premises, which are characterized by tightness and the absence of a constant stay of people. This is due to the fact that fire extinguishing gas is an extremely dangerous substance for human life and health. However, this method of extinguishing, in comparison with the others, causes minimal damage to the room and the equipment located in it. That is why it is most often used to extinguish server and other premises in which damage to expensive equipment is unacceptable.

Autonomous gas fire extinguishing system using S2000-ASPT

In this case, the room equipped with a gas fire extinguishing installation has a raised floor and a suspended ceiling. Since these spaces are separate independent volumes, fire alarm loops and pipe leads are installed in them, through which, in the event of a fire, the extinguishing agent will be supplied. The principle of the system is as follows. When the s2000-ASPT receives a signal from the detectors about the detection of a fire, the device will start the light and sound alarms, after which it will start counting the delay time for the start of the extinguishing agent. If during this time the start is not canceled, the device starts supplying the extinguishing agent. Blocking the start of extinguishing is performed by the door control sensor when entering / exiting the room. It is also possible to cancel the start of extinguishing by turning off the automatic mode from the reader connected to the S2000-ASPT.

The operation of a centralized system is somewhat different from an autonomous one. In this case, it is assumed that there are several fire extinguishing zones with a common gas battery (main and backup) and piping through which gas is supplied to each zone. A separate S2000-ASPT is installed for each of the zones. All devices are connected by an RS-485 interface with a network controller and other devices located in the fire post or at the security post. In such a system, the functions of starting extinguishing are divided between the S2000S network controller and the S2000-ASPT device as follows. When a fire occurs, the S2000-ASPT generates a "start" signal, after which it opens the shut-off valve included in its starting circuit. The S2000M bullet, after receiving a message about the start of extinguishing in a given direction, activates the S2000-KPB outputs, which open the set number of cylinders of the installation. Further, the gas flows through the pipeline into the room. When the set value of the gas pressure in the pipeline is reached at the entrance to the room, the pressure alarm will work, after which the S2000-ASPT sends a message to the S2000M about extinguishing in the given room. If the S2000-ASPT does not detect the triggering of the signaling device, the message "unsuccessful start" is sent to the S2000M, which in turn activates the S2000-KPB outputs, which are responsible for opening the reserve cylinders. Thus, the system works out the control of the redundant extinguishing installation, which significantly increases the efficiency of the system as a whole.

Control device for powder, aerosol or gas fire extinguishing in one direction (24V / 1A, up to 2A for 2 seconds), together with S2000-KPB - up to 97 directions. Work autonomously or as part of the Orion ISO

Description S2000-ASPT

S2000-ASPT Fire extinguishing control device

Parameters S2000-ASPT

  1. designed for autonomous or centralized (as part of the Orion system) fire protection of industrial and civil facilities in one zone of powder, aerosol or gas fire extinguishing
  2. monitors states
  1. three conventional fire alarm loops
  2. fire extinguishing agent output control circuit (OTV)
  3. remote start circuit
  4. chain of serviceability of equipment of the fire extinguishing installation

Specifications S2000-ASPT

Parameter name
Number of loops 3
Light indication27 LED indicators
Backup power2 batteries, 12 V, 4.5 Ah
Built-in buzzer not less than 50 dBA
Fire extinguishing control devices
Control device for powder, aerosol or gas fire extinguishing in one direction (24V / 1A, up to 2A for 2 seconds), together with S2000-KPB - up to 97 directions. Work autonomously or as part of the Orion ISO. Outputs to sirens: СО1 "Go away", СО2 "Do not enter", СО3 "Auto disconnected", ЗО "Sirena" - 24V / 1A. Output NO-C-NO = 28V / 2A (~ 128V / 0.5A). Outputs "Fire", "Fault": = 100V / 0.1A (NR), Power output. 24V / 0.2A. U-pit. ̴220V / 50 Hz; case for two batteries 12 V / 4.5 Ah; R-cons. 30VA; IP30; 305x255x95 mm; 6.0 kg
Control and starting block with 6 executive relays. Control from "S2000-ASPT", "S2000" or "Orion" workstation
Fire extinguishing system indication unit for operation in the ISO "Orion" system, 32 status indicators for 4 fire extinguishing directions, 4x4 seven-segment start delay indicators, 8 generalized fire extinguishing installation status indicators, 6 unit status indicators, RS-485, TM port, 10.2-28 , 4 V, power consumption no more than 3 W, IP20, 170 × 340 × 25.5 mm
Addressable remote control element for S2000-KDL with built-in short circuit isolator, up to 40 EDU for S2000-KDL, I-consumable 0.6mA, IP41, 94x90x33mm
Addressable EDU for S2000-KDL, I-consumer 0.5mA, IP41, 94x90x33mm, green
Addressable EDU for S2000-KDL, I-consumer 0.5mA, IP41, 94x90x33mm, orange
A device for controlling the equipment of a pumping station of a sprinkler, deluge, foam fire extinguishing or fire water supply system. Usup.220V, under the battery 7Ah, IP30, 305x255x95mm
Control and indication unit of the Potok-3N device status, 17 sections, 50 indicators, RS-485, Upit 10.2-28.4V, Ipotr.200mA, 170x340x25.5mm
Control and starting cabinet, wall-mounted, hinged, 4 indicators, Usup.380V (3-phase), Pconsum 30W, Iswitch 10A (nominal), Pmotor 4kW, IP30, 400x400x170mm, 20kg
Control and starting cabinet wall-mounted, hinged, 4 indicators, Usup.380V (3-phase), Pconsum 30W, Icommut.25A (nominal), Pmotor 10kW, IP30, 400x400x170mm, 20kg
Control and starting cabinet, wall-mounted, hinged, 4 indicators, Usup.380V (3-phase), Pconsum 30W, Icommut.63A (nominal), Pmotor 30kW, IP30, 400x400x170mm, 20kg
Control and starting cabinet wall-mounted, hinged, 4 indicators, Usup.380V (3-phase), Pconsum 30W, Icommut.100A (nominal), Pmotor.45kW, IP30, 600x400x240mm, 30kg
Control and starting cabinet wall-mounted, hinged, 4 indicators, U-supply 380V (3-phase), P-power 50W, I-switch 432A (nominal), Rdvig. 110 ... 250kW, IP54, 1000х500х350 mm, 70kg
Reserve input cabinet, two inputs, input voltage 380 V, rated switching current 65 A, power consumption 30 W, two control relays, IP54, 500 × 400 × 200 mm
Reserve input cabinet, two inputs, input voltage 380 V, rated switching current 225 A, power consumption 30 W, two control relays, IP54, 700 × 600 × 240 mm
Reserve input cabinet, two inputs, input voltage 380 V, rated switching current 500 A, power consumption 30 W, two control relays, IP54, 900 × 800 × 280 mm
LLC "OPT Security"

S2000-ASPT control and reception device for autonomous and centralized fire systems based on ISO "Orion" from Bolid. The device is designed to provide protection to one direction of fire devices (gas, aerosol or powder).

It can be used for manual, remote and automatic control of fire extinguishing installations. The device is capable of receiving and distributing notifications from fire detectors connected to it. Carries out control of light and sound annunciators, ventilation systems.

It can be connected to the alarm notification interface through the network controller.

General information

The control unit and control unit for automatic fire extinguishing means "S2000-ASPT" (hereinafter referred to as the unit) is designed to work as part of an automatic installation for gas, powder, aerosol fire extinguishing or extinguishing with water mist. The operation of the unit is possible only in ISO "Orion" under the control of a network controller (console "S2000M") together with an indication unit of the fire extinguishing system "S2000-PT".

The block is intended for:

  • protection of one direction of fire extinguishing;
  • control of an automatic fire extinguishing installation (AUP) in automatic and remote modes;
  • receiving and processing signals from automatic and manual passive, active (loop-powered) and four-wire fire detectors (IP) with normally closed or normally open internal contacts;
  • control of sound and light annunciators (ЗО and СО). These sirens are not types 1 and 2;
  • management of engineering equipment (shutdown of ventilation systems, etc.);
  • receiving commands and transmitting notifications via the RS-485 interface to the network controller (control panel "S2000M");
  • control of serviceability of control circuits of AUP, light and sound annunciators;
  • control of the serviceability of the automatic fire extinguishing system;
  • receiving notifications from: door state sensors (DS); pressure alarms (CDU); fault outputs ("mass" or "pressure") AUP; control and launch units "S2000-KPB" (hereinafter referred to as the "S2000-KPB" unit); remote start devices;
  • issuing notifications "Fire" and "Malfunction" to the fire station panel (FC).

The unit can be used in conjunction with the S2000-KPB units, which allow to increase the number of starting circuits.

The scope of the unit is to work as part of an autonomous or centralized fire alarm system and installations for protecting premises from fires. The unit is recoverable, controlled, reusable, serviced, multifunctional.

The unit is powered from: main power source (OP) - AC mains, rated voltage 220 V, frequency 50 Hz; backup power source (RP) - two storage batteries, rated voltage 12 V, connected in series.

ATTENTION! It is forbidden to operate the unit without connected batteries!

The unit is designed for round-the-clock operation. The design of the unit does not provide for its use in conditions of exposure to aggressive environments, dust, as well as in explosive and fire-hazardous premises. The design of the unit ensures the degree of protection of the enclosure IP30 in accordance with GOST 14254-96 (IEC 529-89).

In terms of resistance to mechanical stress, the unit corresponds to the LX version according to GOST R 52931-2008 - vibration in the frequency range from 1 to 35 Hz with acceleration up to 4.9 m / s2 (0.5 g). The dielectric strength of the insulation of the current-carrying parts of the unit is at least 1500 V (50 Hz) between the circuits connected to the 220 V alternating current network and any circuits not connected to it.

The electrical resistance of insulation between the circuits specified in clause 1.9 is not less than 20 megohms (under normal conditions according to GOST R 52931-2008). Content of precious materials: does not require accounting during storage, disposal and disposal.

Figure 2.1 Location of indicator lights

Table 2.2 Purpose and modes of illumination of indicators of the "S2000-ASPT" block

Purpose and parameters of external devices control outputs

Location of S2000-ASPT block buttons and their purpose

On the front panel of the unit there are 17 function buttons and an electric contact lock. The location of the buttons is shown in Figure 2.2. The purpose of the buttons is shown in Table 2.3.

Product composition

The scope of delivery of the unit is shown in Table 3.1. The unit is supplied without rechargeable batteries. Supply of storage batteries 12 V - 4.5 [A * h] is carried out under a separate agreement.

Table 3.1 Delivery set of S2000-ASPT block

Marking

Each block is labeled as follows:

  • block symbol;
  • the last two digits of the year and the quarter of manufacture;
  • conformity mark;
  • factory number.

The marking of the external terminals of the unit corresponds to the circuit diagram.

Next to the mains block there is an inscription with the designation of the nominal value of the supply mains voltage. The unit housing has a terminal for connecting a protective earth.

Package

The unit is packed in consumer packaging - a cardboard box, which contains a set of spare parts and operational documentation for the unit.

Packing of blocks in containers according to GOST 9181-74 is allowed.

Preservation of blocks should be carried out in accordance with GOST 9.014-78 for product group III3 with a variant of temporary anti-corrosion protection VZ-0.

Boxes with packed blocks, spare parts list, group spare parts are packed into a shipping container - a box of type II-I GOST 5959-80.

Each box (or container) must include a packing list containing the following information:

  1. manufacturer's trademark;
  2. name and designation of blocks, their number;
  3. designation and quantity of spare parts;
  4. signature or stamp of the person responsible for packaging;
  5. packing date.

General operating instructions

To ensure the declared characteristics, the unit should be operated with connected and charged batteries.

After opening the package, it is necessary to: conduct an external inspection of the unit and make sure that there are no mechanical damages; check the completeness of the unit.

After transportation, before being switched on, the unit must be kept unpacked under normal conditions for at least 24 hours.

Indication of safety measures

When installing and operating the unit, one should be guided by the provisions of the "Safety Rules for the Operation of Consumer Electrical Installations" and "Rules for the Operation of Consumer Electrical Installations".

To work on assembly, installation, inspection, maintenance of the unit, persons who have a safety qualification group of at least III for voltages up to 1000 V must be allowed.

Do not use inappropriate fuses and do not operate the unit without grounding.

All installation work related to troubleshooting should be carried out only after disconnecting the main and backup power supplies to the unit.

When working with the unit, remember that the “~ 220 V” terminals may be energized and dangerous.

Installation procedure

The unit is supplied by the manufacturer in the following configuration:

  • batteries are not installed;
  • jumpers XР1, XР2 are installed;
  • tamper switch connected;
  • configuration parameters correspond to tables 2.12–2.15.

To change the configuration parameters, you need to perform the following operations.

Connect the unit to a personal computer through one of the interface converters: S2000M (in programming mode), PI-GR, S2000-PI, C2000-USB or USB-RS485. Use terminals "A1" and "B1" for connection.

Connect the storage battery to the unit. Connect the unit to the network. Wait until the end of the "Switch on" mode of the unit.

Run the program "Uprog.exe". Specify the selected COM-port of the computer and start the procedure for searching for devices. Note: the latest version of the program "Uprog.exe" can be downloaded from the official website of the company "Bolid" http://bolid.ru.

Wait until the program detects the connected block, and select it from the list (if there are several connected blocks).

Change the configuration parameters in the table suggested by the program. Press the button "Save configuration". If necessary, in the "Address" menu item, change the value of the network address of the unit.

When changing the network address of the unit using the "S2000" console, you must perform the following operations.

Wait for the remote control to display a message about the detection of a new unit.

Press the "PROG" button on the remote control. Enter your password. Enter the "Addresses" menu. Specify the current block address. Specify a new block address. The receipt of the successful assignment of a new address is a double short beep of the remote control when pressing the "ENTER" button.

When the unit is connected to the network of the Orion integrated security system, as well as when several S2000-KPB units are connected to the RS-485-2 input, IT IS NOT ALLOWED THAT TWO OR MORE UNITS HAVE THE SAME NETWORK ADDRESSES! Connect the blocks to the interface line one at a time, assigning each of them a new, individual network address. When disconnecting the unit from the RS-485-1 or RS-485-2 interface lines, DO NOT DISCONNECT ONLY ONE INTERFACE WIRE FROM THE UNIT! DISCONNECT BOTH WIRES!

Connect external circuits to the block terminals in accordance with the diagram given in Appendix B.

Alarm loops are connected to terminals "+ 1-" ... "+ 3-". The detector connection diagrams are given in Appendix B. The number of detectors included in one loop is calculated according to the method described in clause 2.12.1.7. If the AL is not used, then it is necessary to connect an end-of-line resistor to its contacts: 4.7 kOhm - 0.5 W.

The following are connected to the terminals "+ 4-", "+ 6-", "+ 7-", respectively: door DS circuit, OTV output control circuit (SDU) and AUP malfunction control circuit. Any contact detectors or relay outputs of other security alarm devices can be used as status sensors and signaling devices. The connection diagram of the detectors is given in Appendix B. The number of detectors, status sensors or signaling devices that are not powered from the circuit is not limited.

If the circuit is not used, then it is necessary to connect an end-of-line resistor to the corresponding terminals: 4.7 kOhm - 0.5 W.

The circuit of the remote start device is connected to the “+ 5-” terminals. Any UDP operating with devices with constant voltage in the loop can be used as devices. The connection diagram of the detectors is given in Appendix B. If the circuit is not used, then an end-of-line resistor must be connected to the terminals: 4.7 kOhm - 0.5 W.

Light and sound annunciators are connected to terminals "СО1", "СО2", "СО3", "ЗО". Parameters and assignment of outputs for connecting sirens are shown in Table 2.1. The siren connection diagram is given in Appendix B.

IT IS NOT ALLOWED TO LOAD THE OUTPUTS TO THE RATED LOAD WITHOUT CONNECTED BATTERIES!

LOAD CONNECTION MODULES ALLOWING THE UNIT TO CONTROL THE STATUS OF THE SIREN CIRCUIT ARE INSTALLED IN DIRECT CLOSE TO THE SIREN.

DURING COMMISSIONING, AND ALSO, IF ANY OUTPUT IS NOT USED, A RESISTOR MUST BE CONNECTED TO ITS TERMINALS: 1.0 kOhm - 1 Watt.

The AUP start control circuit is connected to the “P” terminals. The output parameters for connecting the control circuit of the AUP launch are given in Table 2.1. If the AUP electric start element requires additional current limitation, then a limiting resistor must be connected in series with it.

The calculated value of the limiting resistor rating is determined by the formula:

Connect the RS-485-1 interface line to terminals "A1", "B1" to work with the network controller. The connection diagram is given in Appendix D.

Connect the RS-485-2 interface line to terminals "A2", "B2" to work with blocks "S2000-KPB". The connection diagram is given in Appendix D.

If necessary, connect the "Fire" and "Malfunction" notification transmission circuits to the VFD control panel to the terminals "FOZH", "FAILURE". The "Fire" notification is transmitted by closing the contacts of the "FOZH" relay, and the "Fault" notification - by opening the contacts of the "FAIL" relay.

To terminals "NO-NC-COM" (terminals "NO" - "COM" are normally open, terminals "NC" - "COM" are normally heating, smoke exhaust, closing air gates, fire dampers, closing and bringing doors, etc.). Output parameters are shown in Table 2.1.

Close the cover of the unit.

Preparation for work

Before working with the unit, it is necessary to study the controls and indications, as well as the technical characteristics of the unit.

  1. Assemble the verification scheme according to Appendix D.
  2. Connect the interface line from the S2000M console to the A1-B1 terminals of the tested unit.
  3. Connect the batteries. Connect the block to the network.
  4. At the end of the “Switch on” mode, the unit should switch to standby mode, and the “S2000M” indicator should display the messages “P127 DEVICE DETECTED” and “P127 DEVICE RESET”.
  5. Translate lock lock. If the unit is in any of the alarm modes, by pressing the "Fire reset" or "Fire extinguishing reset" buttons, switch it to standby mode. If indicator 6- "Automation is off" is on, turn it off by pressing button 3. Indicator H8 should turn on.
  6. Press and hold down the S1 button. The H1 indicator should turn off for 3 s, the AL2 indicator should intermittently turn on in red, and the “S2000M” indicator will display the message “SENSOR OPERATION 127/002”. In 2 seconds after the H1 indicator turns on again, the unit should switch to the "Attention" mode, and the "ATTENTION 127/002" message will be displayed on the "S2000M". The H4 indicator will turn on.
  7. Release the S1 button and press the S2 button. The SHS3 indicator should turn on intermittently, and "S2000M" will display the messages "SENSOR OPERATION 127/003" and "ATTENTION 127/003". Release button S2.
  8. In 2 seconds the unit will switch to the “Fire” mode, the “FIRE 127/010” message will be displayed on the “S2000M”. The H3 indicator will turn on continuously, and the H9 indicator will turn on intermittently.
  9. Press button 3 - "Automatic" on the front panel of the unit. The automatic start mode will turn on, and the unit will go into the "Start delay" mode. On "S2000M" messages will be displayed: "AUTOMATIC ON. 127/009 "," START DELAY 127/010 ". The H8 indicator will turn off and the H6 indicator will turn on intermittently.
  10. Short-circuit the door DS circuit: "+ 4-". The block will switch to the "Start blocking" mode, the "S2000M" messages will display "SHORT CIRCUIT. 127/004 "," BLOCKER. START 127/010 ”,“ AUTOMATIC OFF. 127/009 ". Indicators H2, H8 will turn off.
  11. Restore the chain of the DS door. The "S2000M" will display the message "RECOVERY. TECHNOL. ШС 127/004 ", and after 3 seconds the H2 indicator will turn on.
  12. Re-enable the automatic start mode by repeating steps 9). The block will switch back to the "Delayed start" mode. On "S2000M" messages will be displayed: "AUTOMATIC ON. 127/009 "," START DELAY 127/010 ". After 30 seconds, the unit will switch to the "Start" mode, the H5 indicator will turn on and the automatic start mode will turn off. "S2000M" will display the messages: "START AUP 127/010", "AUTOMATIC OFF. 127/009 ". The H6 indicator will turn off, and the H7 indicator will turn on in intermittent mode.
  13. After 15 seconds the indicator H5 will turn off, "S2000M" will display the message "FAILURE START 127/010". Note. A message about an unsuccessful start was generated, since no violation of the control circuit of the OTV output was recorded during the start pulse.
  14. Press button 2- "Extinguishing reset", then press button 1- "Fire reset". The unit will go into standby mode. "S2000M" will display the messages: "CANCEL STARTING" S2000-ASPT "ATsDR.425533.002 RE Rev.17 ATsDR.5578-17 from 29.06.2017 43 127/010", "RESET ALARM AL 127/002", "RESET ALARM AL 127 / 003 "," TAKE SHS 127/010 "," TAKE SHS 127/002 "," TAKE SHS 127/003 ".
  15. Disconnect the unit from the mains (remove the holder with fuse F1). Within 1 minute, the unit must go into the "Standby" mode. When switching to the "Reserve" mode, the H2 indicator will turn off, and the "S2000M" will display the message "ALARM 220V 127/007".
  16. Restore the mains supply to the unit. The unit should return to standby mode, the "S2000M" will display the message "RECOVERY. 220V 127/007 ".
  17. Disconnect the red wire from the battery. Within 15 minutes, the unit must switch to the "Reserve emergency" mode. When switching to the "Backup emergency" mode, the H2 indicator will turn off, and the "S2000M" will display the message "BATTERY FAILURE 127/008".
  18. Reconnect the red wire to the battery. Wait 15 minutes or press button 1- "Fire reset". The unit should return to standby mode, the "S2000M" will display the message "RECOVERY. BATTERIES 127/008 ".
  19. Disconnect the battery. Disconnect the mains supply to the unit. Close the cover of the unit. Translate lock lock.

Operating procedure

Persons who have studied this Operation Manual, the operation manual for the S2000 console ATsDR.426469.005 RE, S2000M ATsDR.426469.027 OM, as well as labels for the S2000-KPB unit ATsDR.425412.003 ET are allowed to work with the units and "S2000-PT" ATsDR.426469.015-02 ET (when working together with these devices).

The number of fire extinguishing starting outputs can vary from 1 to 97, depending on the number of connected S2000-KPB units (up to 16). The "S2000-KPB" addresses connected to the RS-485-2 input can coincide with the addresses of the devices connected to the RS-485-1 input. The numbers of the S2000-KPB blocks used to increase the number of starting circuits must be specified in the S2000-ASPT block configuration.

Remote control and monitoring of the unit status can be realized using the indication and control unit "S2000-PT". For this, the network controller must be configured accordingly.

Uprog configurator

PPPU connection diagram

Programming

To program the settings, you need to connect the S2000 ASPT to the computer through one of the devices:

  • S2000M (programming mode must be enabled)
  • PI-GR
  • S2000-PI
  • S2000-USB
  • USB-RS485

During a fire, there is a need for instant and centralized actions to prevent a negative situation. For this, as well as preventive measures, a control and receiving device for controlling fire extinguishing means and sirens S2000-ASPT was developed in auto mode.

Block purpose

The control device has the ability to prevent the spread of open fire over a certain area of ​​the premises, into which fire extinguishing materials will be supplied at equal intervals, or all at the same time. Automatically or remotely, it controls a fire extinguishing device that uses powder, gas or aerosol.

According to the instructions, ASPT S2000 has the ability to receive instructions and transmit alarm information to network controllers of such types as S2000 and S2000M or the Orion complex. The unit receives and processes information signals from detectors that can operate in an independent, manual or active type of power supply. Carries out management activities for working with sirens based on light and sound capabilities. Takes control over the engineering equipment of the premises, including ventilation. S2000-ASPT monitors the operability of the automatic fire extinguishing system, monitors all types of sirens, receives information from door sensors and pressure signaling devices.

System capabilities

It has a built-in function to transmit information such as fire and malfunction to the control panels of the fire extinguishing unit on duty. Used as an addressable unit in the jointly integrated Orion mode. To increase the starting chain directions, it is used with the S2000-KPB system. The S2000-ASPT device operates in the field of fire alarms with an autonomous or centralized mode of protecting buildings from fires.

The device is subject to restoration work, can be serviced, has the ability to be used repeatedly, is controlled and has multiple functionality.

This system is powered by two options:

  1. The main source is the 220 V, 50 Hz AC power grid.
  2. Alternative power supply can be provided by two 12 V batteries in series.

The operating instructions for the S2000-ASPT indicate that the system has the ability to work around the clock. It is not recommended to use the device when exposed to aggressive media.

Technical specifications

C2000 covers one open fire extinguishing zone with its functional resources. Equipped with three alarm loops. In its branching, it accommodates 8 switched circuits per single fire area.

Together with the S2000-KPB devices, it includes about 97 outputs in its structure for activating automatic fire extinguishing installations, without them there is only one output.

Light-based sirens are controlled by three outputs. In this case, the board is equipped with characteristic signals "LEAVE / DO NOT ENTER / Automation is disabled". For one output with the signal "Siren" is provided. Engineering equipment, according to the instruction S2000-ASPT, has one output.

The control circuits have received 10 inputs in the system design. They include:

  • 3 alarm loops;
  • 1 door chain;
  • 1 sequence of manual start sensors;
  • 1 input of a chain of universal pressure alarms;
  • breakdowns are monitored by a circuit with 1 input;
  • serial link of electronic identifier readers - 1 input;
  • RS-485 shell - 2 inputs.

The operating temperature of the S2000-ASPT is from 0 ° C to +55 ° C. Has overall dimensions 310x254x85 mm and weighs about 8 kg.

Operation and safety

For the normal functioning of the entire system, it is necessary to carry out work with connected and fully charged batteries.

After unpacking the equipment, you should pay attention to the absence of mechanical damage and check the presence of all parts of the kit by visual inspection. Before activating the device, it must be stored in normal conditions for a day.

During the installation and operation of the device, it is worth observing the operating instructions for the S2000-ASPT, as well as adhering to safety measures for working with electrical installations.

Direct installation, inspection, maintenance and other manipulations with the device must be carried out by persons with the permission of the relevant safety qualifications.

Fire extinguishing system connection

Connecting the instrument includes the tasks of changing the data configuration by connecting a computer to the common line interface. This is followed by the connection to the S2000-ASPT of the battery and the AC mains. Wait until the process of turning on the system is over. Using specialized software, start scanning the devices on the computer, select the found device and launch the program to change the configuration parameters by activating the "Write configuration" option.

Also, according to a certain scheme, you need to connect external circuits to the terminals mounted on the device.

Preparation for operation

In order to start working with the S2000-ASPT device, you need to familiarize yourself in advance with the control capabilities, indication signals and technical data of the device. In order to avoid the negative consequences of using the device, a verification test should be carried out for the operability of all components of the system. The required actions are described in detail in the instruction manual.