Connect C2000 bi. C2000 BB Passport - Display Block (C2000 BB)

Landscape design and layout 20.06.2020
Landscape design and layout

Passport and manual

Description and work of the product
1.1 Appointment of the product
1.1.1 The block is designed to be issued to the built-in light indicators and the sound signaling of the notices obtained via the RS-485 interface from the C2000 remote or computer.
1.1.2 The unit can be applied in the Orion system together with the instruments included in its composition. The block is designed for joint operation with devices receiving-control security and fire "Signal-20", "Signal-20P", "C2000-4" and a two-wire line controller "C2000-KDL" and allows the "C2000" or computer through the C2000 console With these devices and controller and display the status of sections controlled by them on the built-in indicators and sound aversion.
1.1.3 The block "C2000-bi" is designed For continuous round-the-clock work in rooms with adjustable climatic conditions in the absence of direct impact of climatic environmental factors.
1.1.4 With autonomous work or with combined autonomous and centralized security, the block allows the control and computer to display an alarm and service messages through the control and control panel to the ORION, and the ORION system devices, as well as the C2000 console operator or computer programming Block configuration parameters, control the blocking status of the display block case.
1.1.5 In resistance to mechanical and climatic influences, the block corresponds to the execution of O3 to OST 25,1099-83, but to work in the temperature range from 274 to 318 K (from +1 to +45) OS.
1.1.6 Block provides messages:
1) "blocking violation" when opening the case;
2) "Reset" when resetting a microcontroller block;
3) "Section status request" when power is turned on.
Issued by the notification unit, at various events (in various
states) are shown in tables 1 - 4 ......

Note - When arriving on a specific partition in a row of multiple messages, a message with a large priority is displayed. The priority of messages are distributed as follows: "Fire", "Attention", "Sabotage", "Fault" for fire sections; "Attack", "Anxiety", "Sabotage", "non-hat" for security and alarming sections. Upon arrival of the message "Removing" the indicator of the corresponding partition turns on
green. When the message "Take" message appears, the corresponding partition indicator is turned on in red.
Table 3 Sound alarm .......

Resetting the sound signal is carried out by pressing the reset button. In this case, the block transmits the "C2000" or computer message "Operator Reaction". The beep can be reset automatically (if specified when configuring the block) after a certain time that can be selected when configuring the unit. In this case, the message is not transmitted when resetting sound to the remote.

Maintenance
The maintenance of the block is made according to the planned warning system, which provides for annual maintenance. Work on annual maintenance is carried out by an employee of the service organization and include:
a) check the external state of the block;
b) performance testing according to section 3.1 of this manual;
c) checking the reliability of fixing the block, the state of external mounting wires, contact connections.
3.1 Product Performance Check
3.1.1 This technique is intended for engineering and technical workers and operators of the OPS serving technical means of security and fire alarm (TC OPS), carrying out the technical condition (input control), and includes an inspection of the block's performance in order to identify defects and evaluating them technical condition. Non-compliance of the block with the requirements specified in this technique,
it is the basis for complaints by the manufacturer.
3.1.2 Checking the technical condition of the unit is organized by laboratories and repair workshops of security departments and is carried out by attendants who have studied the principle of operation of the block and a real methodology and having a qualification of no lower than 3 discharges of OPS electricians.
3.1.3 Check is carried out under normal climatic conditions according to GOST 15150-69:
1) ambient temperature - (25 ± 10) OS;
2) relative air humidity - 45 - 80%;
3) atmospheric pressure - 630 - 800 mm Hg, (84-106.7 kPa).
3.1.4 The check is carried out according to the scheme shown in the application of the total time of checking the technical condition of the block of not more than 20 minutes.
Note - Connecting and disconnecting the wires when checking when the power supply of the block is turned off.
3.1.5 Block check " C2000-bi " Conduct in the following sequence:
a) check the status of the packaging and unpack the unit;
b) Check the delivery package in accordance with the manual
Acedr.426469.015 RE;
c) make sure that there are no mechanical damage to the block;
d) the inspection of the block and shaking it to make sure that there is no inside the case of foreign objects;
e) check the fastening of terminal blocks;
e) Check the compliance of the block number and the release date indicated in the instruction manual.
3.1.6 Procedure for checking the block "C2000-bi" . Before connecting the block to examine its fee for the presence of inter-conducting closures, cliffs of tracks and other mechanical defects. Microcircuits must be installed strictly by key. Install the output voltage of the power supply A1 equal
(10.2 ± 0.3) V.
Turn on the power of the block and the C2000-BE console. There should be an indicator of work. For 1 min, after turning on the console, its indicator should be displayed a message about the detection of the connected block. Measure the current consumption of the block on the ammeter of the RA1.
The measured value should be no more than 0.2 A. The block into the diagnostic mode by pressing 3 times short and 1 time longer on the reset button. This should include a running indication on 60 two-color indicators, 8 system monochrome indicators and should be briefly
turn on the audio signal.
Turn off the devices. Install the output voltage of the power supply A1 equal to (28.4 ± 0.6) V. Repeat the scan.
3.1.7 Record in the journal of repairs and input control of the APS Results on the results of the inspection.

The indication unit is the control panel, which is indispensable in the fire extinguishing system during autorun. The C-2000-bi model is capable of connecting to the control unit through the standard RS-485 interface. Also, the C-2000 model makes it possible to connect a computer as a control unit with the presence of a special process for this process. In addition, the C-2000 model is capable of connecting to the Orion system nodes.

This model has 60 indicators that are two-color. They are intended to monitor individual objects. Each indicator is able to show the state in which the controlled partition is located. Also, C-200-bi accepted and displays messages in text format. To read, and view text messages, serve 8 indicators that are colorless.

Appearance

The C-2000-bi indication unit has a metal case with an indicator. In the printed circuit board, which is located in the block of the block, there are elements of the radio. Wires are attached to the screw, there are special pads for this.

Also in the block exist nodes. The block nodes include a sensor that reports that the housing is opened. The block nodes include, alarm, indicators that are LED. Memory that depends on energy, and the button by pressing it is resetting the alarm.

The C-2000 B B block processor is an indispensable part. The processor accepts messages. Also indicators and signaling sound are under the control of the processor.

Currently, Iso Orion, these are devices and devices associated with functions. The total number of devices and devices 116, and the presence of 33 programs. Combining all these elements for the protection of a particular facility from fire, and video camera management, in one word, to ensure safety.

It is necessary to know that the storage of the device in places in which acidic pairs and gases are present, as well as other harmful substances that can cause corrosion. Also storing the device in the package, without making conservation, allowed to one year, and no more.

Application area

The model C-2000-bi indication block is created to work together with the control panel in Orion. The composition of Orion includes C-2000 control, as well as embedded indicators, thanks to which the display is made. Alarm that reports changes.

Display, which is performed on indicators, show a state in which there are subjects under control. (Malfunction, taken, attention, taking, fire, removed, attack, anxiety).

The listed alarms are shown on the indicators that are affiliated with the C-2000-bi indication unit.

If you receive a message about alarm on sections that are under control, sound alarm is triggered. The operator can reset it. Also, when hacking the case of the remote control, the message arrives.

Specifications

The block size is 340s 170 mm, 127 devices can be connected.

For electrical power, the display unit requires a source with a voltage of 10.2-28.4 V. The power for the block should not exceed 3 W.

In each block there is a configuration. In the C-2000-bi display unit, the configuration is a network address, it includes partition numbers that are controlled, as well as the type of block.

The network address is needed to contact through the interface. While connecting the block to the network, its address must be unique.

Using management, as well as the control panel, the configuration can be changed. Also, to change the configuration, you can use the computer and a special interface converter.

The program called UPROG.exe Number, which is 4.0.0.312. Use to enter the necessary parameters to the computer.

Where to buy and how much costs

There are many shops in which there is a wide selection of display units. Also any indication block can also be purchased by ordering in the online store. When buying in the store at your request, without departing from the box office, experts can change the configuration. Nevertheless, there are different types of blocks and each type has its own price.

The indication unit from the producer "Car" is popular. Buying this block is carried out in retail, small wholesale, and wholesale. The price when buying retail is 4,392 rubles. When buying small wholesale, the price reaches 4224. The purchase price that is produced in bulk reaches 4055 rubles. You can buy this block in the store and through the online store.

Also in online stores and in warehouses, you can purchase a C-2000-bi indication unit from the producer "Car" for 4000 rubles, 3660, 2890, 4684. Prices are quite diverse depending on the display of the indication block. In general, the price of blocks from about 2500 to 12,000 rubles.


Installation and Setup

When configuring the display unit, security measures are required:

  1. During installation, it is necessary to turn off the block from the power supply. 2. Title when installing the unit should also be disabled from the power source.
  2. The unit must not be connected to the voltage and in the process of maintenance.
  3. Conduct the unit installation, as well as maintenance, is allowed only to persons who handed over safety exams, and received a group not lower than the third.

All listed rules are important, non-compliance may be incorrigible to your health and life consequences.

Before connecting the unit, you must configure it, that is, installing the network address, enter the task you want to set the time when the sound alarm will have to work. Devices connected to one interface should not contain the same addresses. You still need to set the block type, this is, for example, cool or other. Also must establish a relationship between sections.

It is desirable to install an indication unit on the wall of the room, which is under guard. Atmospheric precipitates adversely affect the block, so it must be protected from them. Also, the unit must be installed so that unauthorized persons do not have access to it.

After the block was attached to the appropriate site, it is necessary to carry out the unit.

At the same time, as already mentioned, it is necessary to follow the rules. Then connect the connecting lines.

In the process of connecting to the interface, the indication unit is required to have "A and B" contact. Also, for this procedure, it is required to have a connected to the lines. The interface contributes to connecting all devices simultaneously in the interface. This requires installed on the devices of the first and last resistors. The line interface must be voltage not higher than 200 ohms.


Benefits

  1. Convenience.
  2. Reliability.
  3. Benefit.
  4. The C-2000 bi-bi indication unit is suitable for any premises, for small and large. After all, if the room in which the block will be installed is small, then one device will be enough for it. In the event that the room is large, then this is also not a problem. After all, you can use several devices by combining them with a network controller. In large premises, experts advise the use of special programs. In the presence of features there will be more. Programs will include the desired alarm on the divisions, if necessary, the security alarm will be activated, in the event of a lighting, fire alarm is included, and along with this fire extinguishing. Also programs will be monitored by parking, behind engineers systems, and observations are carried out. Also, the alarm is ensuring that the instruments that are notified of one or another problem are not dreamed.
  5. Reliability guarantees the production that produces these devices. For 20 years of work, this production has already installed its devices on more than 700,000 objects. The unit must serve at least 10 years. Term Operation of a year and a half. Repair of the device is carried out only if there is an act with faults.
  6. In these devices there is a train. Depending on the loop, the device will guard the room. Trades are different, choosing suitable for its area, payment is made depending on your area, which is very profitable.

This device is intended for use as part of a fire alarm system to display a state of 60 sections in an integrated Orion Object Protection System.

Features of the Interface Display Block C2000 BB SMD manufactured by BOLID:

Additional devices in the security and fire alarm of the C2000 series have stable characteristics, and refers to the discharge of "universal auxiliary devices".

The ability to display on each of the 60 two-color indicators of the status of sections taken under control. Display alarm: not connected, taken, wear, removed, quiet anxiety, anxiety, malfunction, attention, fire.

Displaying on 8 monochrome LED indicators (system) on a block of indication of a variety of notices, such as: non-hat, anxiety, quiet anxiety, malfunction, attention, fire, blocking violation, communication violation via the RS-485 interface.

The presence of a special place to sign the name of the controlled partitions of the OPS.

Enabling the built-in audio signal when you receive an alarm message both in one and several controlled sections and with the ability to reset it with the operator.

The configuration feature allows you to display in different ways of states for security and fire modes of controlled sections.

Sending a message of the message on the inclusion of the indication block, hacking the C2000-bi body to the C2000 console, C2000m or a personal computer under the work of the Orion protection system.

The non-volatile memory of the indication block has the ability to assign a network address, assigning partition numbers (the state of which displays bi), record configuration parameters.

Modern design, simplicity of installation work will delight both specialists in installing low-current systems and business owners who have decided to establish a modern address system to their object.

A wide range of instruments for the brand Bolid brand allows you to make a choice of model for any request and functionality. A large selection will delight companies engaged in the installation of fire and security alarm systems and their customers. Although C2000-bi SMD and refer to the category " cheap OPS Indication Blocks"He is reliable, like all the other elements of the brand" BOLID ".

Specifications C2000 BB SMD (BOLID)

Name of parameter The value of the parameter
. Light indication

60 two-color indicators to display the states of the ISO ORION sections

7 single-color indicators for displaying alarm and malfunction in ISO "Orion"

1 indicator to display block operation modes

. Built-in sound signaling there is
. Sensor opening the case microswitter
. Communication port (for work in ISO "Orion") RS-485, Orion Protocol
. Block power

from an external DC source

. Supply voltage 10.2 ÷ 28.4 V DC
. Power consumption not more than 3 W
. Current consumed in alarming mode

no more than 200 mA at voltage 12 V
no more than 100 mA at voltage 24 V

. Current current in standby mode (all indicators are turned off)

no more than 50 mA at voltage 12 V
no more than 50 mA at voltage 24 V

. Readiness to work after power on no more than 2 s
. Operating temperature range from -30 to +50 ° C
. Relative humidity up to 98% at +25 ° C
. Cost protection IP20
. dimensions 340x170x25.5 mm
. Block weight no more than 0.6 kg
. Middle service life 10 years
. Programming device uPROG.EXE program
. Connection to PC via the RS-485 interface using interface converter
. Type of mounting wall mounted

. Alarm for office
. Security and fire alarm for cafes and clubs
. Alarm in the store
. Security systems for warehouse and office space
. Autonomous alarm for apartment, house or cottage
. Fire alarm for indoor car parks, garages and parking
. Complex protection for state institutions (kindergartens, schools, other educational institutions)

Special attention when choosing, take a careful study of the technical characteristics, choosing suitable security detectors, fire detectors, special cable products. The C2000 line devices are one of the best price-quality ratios and are recommended for use in a large spectrum security and fire alarm systems.

Analogs of C2000 BB SMD and other properties similar to the following characteristics:C2000-bi isp. 01 and C2000-BKA.

Buy and order delivery of fire alarm systems in Moscow:

C2000-bi SMD interface converters, as well as other Bolid products (their analogues, detectors, control devices) You can order and buy through the online store of the fire alarm of our site or order delivery and custom installation services in your premises in Moscow in the company " Abars. (Attention, delivery is free when ordering over 60 thousand rubles).

We recommend to read

Top